Hydrant Flow Test Report

Two hydrant flow test, rated per NFPA 291
Created at www.HydrantFlowTestReport.com
Test date
4/14/2026, 9:30 am
Conducted by
Example Fire Protection Co.
Agency
Mill Creek Fire Department
Main size
8 in
Available flow at 20 psi
2,311 gpm
Test flow
1,138 gpm
at 58 psi residual
NFPA 291 class
Class AA
Light blue bonnet, 1500 gpm or more
Residual hydrant Flow hydrant The hydrants are 490 ft apart

Residual hydrant

H-1042
Static pressure72 psi
Residual pressure58 psi
Location,

Flow hydrant

H-1043
Location,
OutletPitot pressureDiameterCoefficient
#146 psi2.5 in0.9

Water supply curve

Flow axis scaled to the 1.85 power (NFPA 291 paper), so the supply plots as a straight line
Static 72 psi Test 1,138 gpm at 58 psi Available 2,311 gpm at 20 psi

How the flow was worked out

Each outlet's flow is 29.83 x c x d² x √p (c the outlet coefficient, d the outlet diameter in inches, p the flow pressure in psi). The flow at 20 psi is that flow x ((static - 20) / (static - residual))^0.54, per NFPA 291.

Notes

Example report: the place, the people and every reading are made up to show what a report looks like.